info@ofisistelec.com   |  (+34) 96 144 50 55   |

CPU H226IL 220VAC

128 KB de memoria de programa + 128 KB para librerías de funciones, 64 KB de memoria de datos + 100 KB de memoria de datos permanente, alimentación 220 VAC, 24DI / 16DO relé 2 A, 2 puertos PPI / FPORT, 1 puerto Ethernet. Almacenamiento de datos permanentemente. Soporte control analógico, tarjetas de expansión CAN y RS485, compatible con protocolo S7.

Performance Parameters

Physical Features
Dimension(W×H×D) 196.5×80×62mm
Power consumption 11W
Program memory 128K+64K+64K
Data memory 64KB+100KB,Data permanent stored
Maximum number of expansion modules 7
Maximum digital 128DI/128DO(expand CAN expansion board up to 640DI/640DO)
Maximum analog 32AI/32AQ(expand CAN expansion board up to 194AI/194AO)
Data stored FlashROM Data permanent stored
Power supply features
Rated input voltage AC220V
Impulse current 264VAC,20A
Isolation (field and logic) 1500VAC
Hold time (power off) 20ms/80ms above,120/240VAC
Sensor +24V power output Voltage range:20.4~28.8VDC
Rated current:300mA
Maximum ripple noise (<10MHz) :<1V peak-to-peak value
Isolation (sensor and logic):None
Power alarm when it is lower than 15V, the alarm bit SM195.1
Regular features
Total timers 512
1ms 4
10ms 272
100ms 236
Counters 256
Accumulators 4
Memory bit 256bit
Local storage(L) 64 bytes independent
Sequence control relay(S) 256 bit
Time interrupt 2*1ms resolutions
Edge breaks 8
Boolean operation execution time ≤0.15us
Floating operation execution time ≤6.2us
Real time clock Built-in
BD expansion board port One ,BD expansion board supports RS485 expansion board, CAN expansion board, and analog expansion board
System indicator SF indicator (red) ON:Program error,OFF:Normal
DIAG indicator (orange) ON:Program control,OFF:Normal
RUN indicator (green) ON:running,OFF:stopped
STOP indicator (orange) ON:stopped,OFF:running
RMC indicator (green) ON:remote control is connected,OFF:remote control is disconnected
LNK/ACT indicator (green) ON:Ethernet connection,Blinking: Transmission is underway,OFF:disconnect
Run switch RUN/STOP
External battery port 1、Special battery card;2. Professional battery holder (CR1220) supports either external battery
Programming card Support
Integrated communication capabilities (PPI/ free port)
Communication interface 2 Communication port:
PORT0:PPI/free port,standard RS485
PORT1:PPI/free port,standard RS485
After the RS485 expansion board is plugged in and restarted, PORT0 (RS485, PPI communication port) PORT1 (RS485, PPI/ free port), FPORT0 (free port)
Baud rate(baud) 9.6k、19.2k and 187.5k
Free port baud rate(baud) 1.2k ~ 115.2k
Maximum number of stations 32 stations per segment, 126 stations per network
Maximum number of main stations 32
Point-to-point (PPI master mode) Yes(NETR/NETW),With a maximum of 8 connections and a maximum communication of 200 bytes per connection
MPI connect 8(1PG/1OP),2 reserved
Maximum cable length per section

Use an isolated repeater

No isolated repeater is used

The baud rate is 1000 m at 187.5 K and 1200 m at 38.4 K

50m

Ethernet Communication
Communication port 1 Standard Ethernet port
Communication standards IEEE802.3 standards
Transmission speed 10Mbps/100Mbps adaptive
Adaptive cross-connect Support
Hardware interface RJ45
Protocol Type UDP/TCP protocol

Supports UDP_PPI, MODBUS_TCP, Socket, and S7 protocols, Ethernet communication between PLCS, and MiCo Ethernet programming.

Configuration mode Ethernet port search PLC,support the mouth download system configuration.
Maximum number of connections 8 UDP/PPI connections, no master or slave
8 TCP/Modbus connections, no master or slave
4 Socket connections, 2 UDP, 2 TCP
8 S7 protocol, no master and slave, COTRUST PLC only as slave station
Maximum single data transmission Up to 200 bytes for UDP_PPI transmission.
Up to 240 bytes are used for ModBus_TCP transmission.
Up to 512 bytes is used for Socket transmission
Up to 200 bytes for S7 transmission
Startup time of network port 5 to 10 seconds. The startup time varies depending on the network environment.
Indicator RMC On: The remote server is successfully connected
Off: The remote connection is disconnected or the remote function is disabled
LINK/ACT On: The hardware of the network port is connected
Blinking: Data is being exchanged
Off: The hardware of the network port is disconnected
The length of the communication cable 100M,cable type is CAT5e or above
Isolation Communication isolation
IP address reset function Five consecutive times within two seconds
Upgrade Firmware function Use MagicWorks PLC and MiCo to remotely upgrade firmware from company servers over Ethernet
I/O Features
Number of integrated digital inputs 24
Input type Leak/Source
Number of integrated digital outputs 16
Output type Source
Maximum digital 128DI/128DO(expand CAN expansion board up to 640DI/640DO)
Maximum analog 32AI/32AQ(expand CAN expansion board up to 194AI/194AQ)
The maximum number of local expansion IO modules 7
Pulse capture input 14
High-speed counters Total
Uniphase countersAB-phase counters
6
6×50KHz
4×30KHz
Integrated Communication Function (CANopen) – use for CAN communication board model CTH2-CAN-01S2-EB
Communication Interface 1(8 Pin)
Communication speed(kbps) 1000 800 500 250 150 50 20
Maximum cable length(m) 25 50 100 250 500 1000 2500
Maximum station address 127
Station address range 1-127
Maximum number of master and slave stations 32
Configuration method CAN configuration blocks and EDS files
Maximum digital access Nomal IO CANopen IO
Byte Memory starting address Byte Memory starting address
Input 16 IB0 Input 64 IB16
Output 16 QB0 Output 64 QB16
Maximum analog access Normal IO CANopen IO
Channel Memory starting address Channel Memory starting address
Input 32 AIW0 Input 162 AIW64
Output 32 AQW0 Output 162 AQW64
Integrated Communication Function (CANFree) – Used when extending the CAN communication board
Communication Protocol CanFree
Use method Supported by internal library instructions
Digital input features
Number of interated digital input 24
Input type Leak/source
Rated voltage 24 VDC
Maximum continuous allowable voltage 30 VDC
Logic 1 signal (min.) 18 VDC,3.0mA
Logical 0 signal (Max.) 5 VDC,1mA
Isolation (field and logic)

Isolation group

500 VAC,1min
Simultaneously connected input 24
Maximum cable length 500m
Shielding: 50 m (high speed counter input); Unshielded: 300 meters (standard input)
Digital Output Features
Number of integrated digital output 16
Output type Relays, dry contacts
Output frequency (maximum) 100KHz(Q0.0-Q0.2),1KHz(Q0.3-Q1.7)
Rated voltage output 24VDC,or 110V/220VAC
Output voltage range 5-30VDC or 5-250VAC
Rated current per point 2A
Rated current for each common point 8A
Surge current 7A,100ms
Lamp load (maximum) 30W DC/200W AC
On resistance (contact) 0.2Ω
Contact life (rated load) 100,000 times on and off
Output of simultaneously connected 10
Parallel output None
Maximum cable length Shielde 500m
Unshielded 150m

Título